[Home Page] [Research] [Abstracts] [Resume]
[Address] [Education] [Work Experience] [Participated Projects] [Publications]


Research Interests:

Building Energy Conservation

Heating, Ventilating, and Air-Conditioning (HVAC) Systems

Indoor Air Quality (IAQ)

List of Participated Research Projects

  1. Calculations of Outdoor Air Requirements for Air-Conditioning Systems Including Infiltration, Exhaust, and Interzonal Transfer
    National Science Council, Taiwan, ROC, 1999-200.
  2. National Program for Hazard Mitigation
    National Science Council, ROC, 1997-1998.
  3. VAV System Ventilation: Control Strategy Economics
    The Trane Co., La Crosse, WI, 1994-1996.
  4. Real-Time Optimization of Ventilation Control to Minimize Energy Consumption in Variable Air Volume Systems
    Pennsylvania Energy Development Authority, Project No. 93-017, 1995.
  5. The Study and Design Manual of Building Perimeter Annual Load Analysis in Taiwan Area
    Energy Commission, Ministry of Economic Affairs, ROC, Project No. 79211, 1989-1990.
  6. The Analysis of Internal Shading and Desiccant A/C System on Building Energy Conservation Design in Taiwan Area
    Energy Commission, Ministry of Economic Affairs, ROC, Project No. 78211, 1988-1989.

Abstracts of Final Reports

  1. VAV System Ventilation: Control Strategy Economics
    prepared by S. A. Mumma, Yu-Pei Ke, and S. P Sevigny
    sponsored by The Trane Co., La Crosse, WI, 1994-1996.

    The concern over the perception that the US energy supply is bounded led building mechanical system engineers to take many measures to reduce energy consumption in buildings since the 1970's. Among the measures was a significant reduction in the ventilation air provided to building occupants. As a result a whole host of building induced illnesses surfaced. In response, ASHRAE developed Standard 62-1989 "ventilation for acceptable indoor air quality". The standard set a ventilation rate per person which went counter to the energy concerns of the day. Ever since engineers and researchers have been seeking the best ways to provide acceptable IAQ with minimal energy consumption.

    The piece of research presented in this report provides an automatic control approach to ameliorating the conflict between energy use and acceptable IAQ in buildings served with variable air volume mechanical systems. Eight control strategies are investigated, and the resultant quantitative measure of IAQ and energy consumption documented. Several of the controls employ optimization techniques in real time to achieve the desired results. The research consists of 2 major portions, an analytical piece and an experimental field evaluation piece.

    In both the analytical and experimental pieces of the research, a Central Pennsylvania library building was used as the focus of the work. Detailed models of the building and its mechanical systems were developed. The models were used to simulate, on an hourly basis for an entire year, the building and its systems located in 6 different geographic locations and operating under each of the 8 control approaches. Three of the best control approaches, each able to meet the ventilation requirements at acceptable energy consumption levels, was implemented into the library building and data collected under various weather conditions to confirm the analytical predictions.

    The analytical results reveal that the control which optimizes outdoor air flow and supply air temperature resulted in minimum energy consumption and energy demand while providing acceptable IAQ. The analytical work was confirmed by the field study.


  2. Real-Time Optimization of Ventilation Control to Minimize Energy Consumption in Variable Air Volume Systems
    prepared by S. A. Mumma and Yu-Pei Ke
    sponsored by Pennsylvania Energy Development Authority, Project No. 93-017, 1995.

    This energy improvement research project explored the potential to simplify the real-time on-line optimization control for building variable air volume (VAV) mechanical systems. The research was undertaken in the context of the AMP Headquarters building located in Harrisburg, PA. The research revealed that in the AMP building 27% of the zones were never critical and could thus reduce the complications of the control. It was further found that by forcing some critical zones to be non-critical (accomplished by elevating the VAV box minimum primary airflow rate settings) the system could be further simplified with 39% of the zones now non-critical without an increased energy penalty or indoor air quality (IAQ) problem. Forcing more zones to never be critical rapidly caused the energy advantages the real-time on-line optimization control to decrease. The team is interested in continuing this research by moving from the analytical to experimental phase.

    A complete implementation of the real-time on-line optimization control in commercial buildings employing VAV air-conditioning systems, to minimize energy demand and consumption while meeting the strict IAQ standards required by ASHRAE Standard 62-1989, is estimated to result in Pennsylvania energy savings in excess of $40 million per year when compared to other possible ways of meeting the standard. An incalculable improvement in worker productivity and a reduction in costly litigation from sick building syndrome is also expected.


  3. The Study and Design Manual of Building Perimeter Annual Load Analysis in Taiwan Area
    prepared by Kuan-Hsiung Yang, H. T. Lin, Yu-Pei Ke, R. L. Hwang, and K. J. Tou
    sponsored by Energy Commission, Ministry of Economic Affairs, ROC, Project No. 79211, 1989-1990.

    After the worldwide energy crisis in the 1970's, building energy conservation attracted a lot of attention and research efforts. In 1975, the first energy code was established in the US, which utilized the Overall Thermal Transfer Value (or abbreviated as OTTV) as an energy efficient criteria and design guide in evaluating the thermal performance of building envelopes. The OTTV standard was again widely applied in ASEAN countries, especially Singapore and Thailand with success.

    In adapting the OTTV standard and probing its applicability in Taiwan, a thorough parametric analysis was performed in this study. Ten years of weather data in Taiwan were compiled into an Average Weather Year, and 46 typical existing buildings in major cities of the country were analyzed. Followed by applying the orthogonal array analysis, the reference OTTV values in Taiwan to be adapted in energy codes were completed.

    A new index Envelope Cooling Load Value, or ECLV, was originated during this research, which is based on a more profound dynamic air-conditioning load theory. It was justified to be more reliable in reflecting building thermal performances, after carrying out the same analytical methodology as in OTTV.

    Finally, the Perimeter Annual Load, or PAL, initiated and applied in Japan, was studied with results compared OTTV and ECLV. The comparison among these 3 indexes was performed to justify their applicabilities in Taiwan, and this also provided valuable information on building thermal performances especially during the design stage. (Content in Chinese)


  4. The Analysis of Internal Shading and Desiccant A/C System on Building Energy Conservation Design in Taiwan Area
    prepared by Kuan-Hsiung Yang, H. T. Lin, R. L. Hwang, Yu-Pei Ke, and H. J. Liang
    sponsored by Energy Commission, Ministry of Economic Affairs, ROC, Project No. 78211, 1988-1989.

    This project is the third phase of a long-term project on building conservation study sponsored by the Energy Committee of Taiwan. In this year, the topics are the analysis of energy savings of (1) a passive design strategy--internal shading, and (2) an active system--chemical dehumidification encoupled hybrid cooling system.

    The study was first focused on "internal shading." Through the dynamic air-conditioning load calculation via program HASP8001, the theoretical energy savings of internal shading on buildings in Kaohsiung area can be analyzed. The experiment was then set up on the Energy Test House, room A and room B. Actual tests were conducted in October, June, and July to obtain the actual weather data and air-conditioning power consumption under internal shading, with and without internal loads. It was found that, theoretically, in the 3 months of year, the internal shading would provide 24.0%, 24.6%, and 31.9% energy savings, respectively, under no internal load condition. These values only deviated from the experimental results by 13.5%, 5.1%, and 8.8%, respectively. This result is within engineering tolerances and thus quite satisfactory. The validation of the mathematical model can only be performed under the same operation conditions as stated above. After the HASP validation was completed, the AYWD (Average Year Weather Data) of the 6 large cities in Taiwan, namely, Taipei, Taichung, Tainan, Kaohsiung, Taitung, and Hualien, compiled during 1987's project, were then input into HASP to evaluate the energy savings.

    It was found that, under normal air-conditioning system operation conditions, the annual energy savings in imposing internal shading are 2.3%~3.7% only. This is quite insignificant, especially when compared with the "external" shading that was evaluated in an earlier phase of this long-term project. It is also concluded that, in Taiwan area, more efforts should be emphasized on external shading design, instead of internal shading.

    On the other hand, in analyzing the chemical dehumidification system, the study was conducted through computer simulations and experimental investigations by manufacturing a prototype system. The verification was successful, which warrants further long-term research on this system in the future.

    The mass and heat transfer phenomenon involved during the chemical dehumidification process was theoretically formulated into a mathematical model. The model was then numerically analyzed through Runge-Kutta scheme. The analysis indicated that the predominant factors in affecting the performance of a chemical dehumidifier are the outdoor air conditions, rotational speed, air face velocity, and silica-gel regeneration temperature. The theoretical analysis was validated by actually manufacturing a prototype desiccant drum using silica-gel. The experimental results yielded only a low 10% deviation, compared with theoretical results. The other components of the system were also analyzed, such as the thermal wheel, which showed that 83% effectiveness can be achieved. This condition occurred with an optimal rotational speed at 12~16 RPH, while the evaporative cooler was having an average outlet air wet bulb temperature of 23 C because of the high humid weather in Taiwan.

    According to the original plan stated in the proposal, only the chemical dehumidification system, composed of a desiccant drum with evaporative cooler and thermal wheel heat exchanger, would be studied. However, following the successful theoretical and experimental analysis of such a system, which yielded 8%~10% deviation only, the research team was encouraged to extend the study of another hybrid system, whose evaporative cooler was replaced with a conventional vapor-compression air-conditioner. The result was more successful. The comparison of the experimental and theoretical results indicated 5% deviation only.

    The successfully validated simulation model developed in this research was then utilized to generate the energy, especially electrical energy, savings in Taiwan area. An average 20.5%~25.3% electrical energy savings can be experienced. The system can be even more effective if the strategy of return and/or fresh air by-pass mixing is utilized in design, which warrants further long-term research in this area. (Content in Chinese)


Send Comments to Yu-Pei Ke: ypke@nkfust.edu.tw
Last construction : December 3, 2001

[Address] [Education] [Work Experience] [Participated Projects] [Publications]
[Home Page] [Research] [Abstracts] [Resume]